| Operating temperature range | A process normally runs from 20°C to 180°C, with occasional excursions to 220°C. | Select an assembly rated for the full expected range, including startup, shutdown, and excursions. Industrial platinum RTD elements may cover approximately −200°C to 850°C, but the complete sensor assembly may have a narrower limit. | Check the element, sheath, cable, seal, connector, and transmitter temperature limits—not just the PT100 element range. |
| Required accuracy | A monitoring point near 100°C needs approximately ±0.5°C sensor tolerance. | For IEC 60751 tolerance equations at 100°C, Class A is ±0.35°C and Class B is ±0.80°C. Class A meets the stated sensor-tolerance target; Class B does not. | The tolerance applies to the sensing element. Include lead-wire, instrument, installation, and calibration uncertainties in the total measurement error. |
| Wiring distance and lead resistance | The sensor is several metres from the measurement instrument. | Use a 3-wire connection for common industrial installations where the instrument supports lead compensation. Use 4-wire wiring when minimizing lead-resistance error is important and the instrument supports it. | Confirm the instrument’s wiring configuration and use compatible cable. A 2-wire connection can introduce significant lead-resistance error, especially over longer runs. |
| Response time | A control loop must react quickly to changes in a moving liquid. | A smaller-diameter probe and a direct-immersion installation generally respond faster than a large probe or a sensor installed in a thermowell. | Request response-time data for the actual probe and installation. Thermowell dimensions, insertion depth, flow, and contact all affect response. |
| Pressure and chemical exposure | The probe contacts a pressurized process fluid that may be corrosive. | Choose a sheath and process connection compatible with the fluid, pressure, and temperature. Use a suitable thermowell where required for pressure containment or sensor replacement. | Verify material compatibility, pressure rating, connection design, and applicable process or safety requirements. |
| Vibration and mechanical loading | The sensor is installed on rotating equipment or in a high-vibration pipe. | Select a mechanically robust probe and mounting arrangement designed for the expected vibration. Avoid unsupported or excessively long insertion lengths. | Check vibration limits, probe dimensions, mounting support, and thermowell suitability with the equipment designer. |
| Measurement-system compatibility | A control system accepts PT100 inputs and uses a specific excitation current and wiring mode. | Choose a nominal 100 Ω platinum sensor that follows the required resistance–temperature characteristic, commonly IEC 60751, and matches the input configuration. | Confirm the standard, nominal resistance, wiring, input range, excitation, and any transmitter or calibration requirements. |