| 1 | DC voltage rating | Confirm that the contactor is rated for the complete battery operating range, including maximum state-of-charge voltage, charging voltage, and transient margin. | Specify the exact system class: 400 V, 500 V, 600 V, or 800 V DC. For an 800 V nominal platform, the requested rating should normally exceed the maximum operating voltage rather than equal the nominal voltage. | Datasheet showing maximum switching voltage, polarity requirements, and applicable voltage derating. |
| 2 | Continuous current capability | Compare the continuous current rating with the actual RMS battery current, enclosure temperature, busbar configuration, and cooling conditions. | Common battery-system ranges include 100–200 A for smaller packs and 300–600 A for high-power packs. Require a defined rating at the intended ambient temperature, not only at 20–25 °C. | Thermal-current curve, conductor arrangement, temperature-rise test results, and derating table. |
| 3 | DC breaking capacity at fault voltage | Do not use the continuous-current rating as the short-circuit interruption rating. Verify interruption performance at the actual DC voltage and prospective fault current. | Request separate tested values at 400 V, 600 V, and 800 V DC. A procurement specification may require, for example, 5 kA at 400 V, 5 kA at 600 V, and 2–5 kA at 800 V, depending on the battery protection design. | Test report identifying voltage, prospective current, circuit inductance, time constant, pre-arcing current, interruption time, and pass/fail criteria. |
| 4 | Make current and inrush withstand | Check whether the contactor can close onto a charged DC-link capacitor or other capacitive load without welding or excessive contact erosion. | Define both the peak make current and pulse duration. A realistic project requirement may include 2–5 kA peak for 1–10 ms, but the value must be calculated from capacitance, pre-charge resistance, and system voltage. | Make-current test data, contact-weld inspection, recommended pre-charge sequence, and maximum permitted switching frequency. |
| 5 | Fault-circuit test conditions | Ensure the test circuit represents the battery’s low-impedance DC source. AC short-circuit data cannot be automatically converted into DC breaking performance. | The report should state the prospective current, circuit time constant, source impedance, cable length, polarity, and interruption waveform. Test conditions should cover the intended 400–800 V DC operating envelope. | Oscillograms showing voltage and current, circuit diagram, calibration records, and laboratory accreditation or competence information. |
| 6 | Contact welding and end-of-life behavior | Verify that the contacts remain electrically open after a severe fault and that normal overload or inrush events do not cause progressive welding. | Require a defined end-of-life condition, such as maximum contact resistance, leakage-current limit, insulation requirement, and successful opening after specified make/break cycles. | Endurance report with electrical cycles, fault cycles, contact-resistance measurements, and post-test photographs or inspection records. |
| 7 | Coil drive and energy consumption | Check nominal coil voltage, pull-in voltage, hold-in power, release voltage, suppression method, and compatibility with the vehicle or battery-management controller. | Typical control options are 12 V DC or 24 V DC. Low-power hold-in operation is often desirable; specify the maximum steady-state coil power and the allowed voltage range, such as 18–32 V for a 24 V control circuit. | Coil voltage-current curve, switching-time data, PWM or economizer requirements, and flyback/surge-control instructions. |
| 8 | Insulation and isolation performance | Confirm clearance, creepage, dielectric withstand, insulation resistance, and isolation-monitoring compatibility for the selected voltage class. | A project may specify dielectric withstand in the range of 2.5–4.0 kV DC or equivalent AC test voltage, with insulation resistance commonly required at or above 100 MΩ. Final values must follow the applicable system standard and pollution level. | Dielectric-strength report, insulation-resistance results, creepage and clearance drawings, and environmental pollution assumptions. |
| 9 | Environmental and mechanical suitability | Match the contactor to temperature, vibration, shock, humidity, dust, salt exposure, altitude, and installation orientation. | A common design envelope is approximately −40 °C to +85 °C for operation, with storage limits extending beyond that range. Require sealed construction where condensation, coolant vapor, or conductive contamination is possible. | Environmental test results, IP protection details, vibration and shock profiles, mounting restrictions, and temperature-derating data. |
| 10 | Documentation and production traceability | Confirm that the supplier can provide controlled drawings, revision history, serial or lot traceability, change notification, and repeatable production-test records. | The purchasing package should include electrical ratings, wiring diagram, terminal torque, tightening sequence, inspection criteria, service life, warranty terms, and a defined change-control period. | Certificate of conformity, production test plan, material declarations, reliability data, quality-system documentation, and sample inspection report. |