| 1 | Rated voltage and supply type | Compare the switch’s marked AC or DC rating with the equipment’s actual supply voltage. Verify the rating for the intended circuit rather than assuming AC and DC ratings are interchangeable. | The switch has an explicit rating suitable for the application’s voltage and supply type. Do not exceed the manufacturer’s stated limits. |
| 2 | Continuous current | Measure or calculate the normal operating current under representative conditions, then compare it with the switch’s rated current for the same voltage and load category. | The operating current remains within the applicable rating. A current rating at one voltage or load type should not automatically be applied to another. |
| 3 | Load type and switching inrush | Identify whether the load is resistive, inductive, capacitive, or a motor. Check starting or inrush current where relevant, and review the switch’s specified ratings for that load type. | The switch is suitable for both steady-state current and switching demands. Resistive-load ratings alone may not establish suitability for motors, transformers, or capacitive loads. |
| 4 | Contact resistance and voltage drop | With the switch closed, measure the voltage across its contacts or use an appropriate low-resistance measurement method. Test at a representative operating current. | Results meet the product specification and remain stable during operation. Follow the specified measurement method, since lead and contact resistance can affect readings. |
| 5 | Insulation and dielectric strength | Use the insulation-resistance or dielectric test method and test voltage specified for the switch and applicable product standard. Isolate sensitive electronics before testing where required. | Measured insulation performance meets the applicable specification, with no breakdown or flashover during the prescribed test. Do not apply an arbitrary test voltage. |
| 6 | Temperature rise and operating environment | Operate the switch under representative load and ambient conditions, then check temperatures at the terminals and relevant surfaces using a suitable measurement method. | Temperatures remain within the switch’s stated limits and the requirements of the applicable standard. Allow for enclosure, airflow, wiring, and ambient temperature effects. |
| 7 | Mechanical operation and endurance | Check actuation, latching or return action, and terminal security. Where required, perform the specified operating-cycle test with the intended electrical load. | Operation remains consistent, connections stay secure, and electrical performance remains within specification after the required cycles. Use the product’s stated endurance test conditions. |