| Power transformers — general requirements | IEC 60076-1 | General requirements, ratings, connections, nameplate information, and test provisions for power transformers. | Rated power and voltage, frequency, phase arrangement, winding connections, impedance, cooling method, and applicable standard edition. | Check that the guaranteed rating and nameplate data match the project specification and approved drawings. |
| Liquid-immersed transformer temperature rise | IEC 60076-2 | Temperature-rise requirements and test methods for liquid-immersed transformers. | Specified temperature-rise limits, cooling arrangement, insulating liquid type, and temperature-rise test results where required. | Confirm that the offered cooling mode and declared limits are consistent with the guaranteed load and site conditions. |
| Transformer insulation and dielectric tests | IEC 60076-3 | Insulation levels, dielectric tests, and external clearances in air. | Insulation-level schedule for each winding and terminal, test list, and routine or type-test reports applicable to the design. | Verify that insulation levels correspond to the specified system voltage and project insulation coordination. |
| Transformer short-circuit withstand | IEC 60076-5 | Ability of a transformer to withstand the thermal and dynamic effects of external short circuits. | Short-circuit withstand declaration, relevant design calculations, and supporting test evidence where available or specified. | Compare the declared withstand capability with the project fault level and protection-clearing time. |
| Transformer routine test documentation | IEC 60076-1; relevant parts of IEC 60076 | Typical routine checks include winding resistance, voltage ratio and phase displacement, impedance voltage and load loss, no-load loss and current, and applicable dielectric tests. | Factory test plan, calibrated-instrument records, signed test reports, and traceability to the supplied unit’s serial number. | Confirm the test scope against the contract; additional tests may be specified for a particular project. |
| AC switchgear — common requirements | IEC 62271-1 | Common specifications for high-voltage switchgear and controlgear, including service conditions, ratings, and general test requirements. | Rated voltage, rated frequency, rated current, short-time withstand current and duration, peak withstand current, and declared service conditions. | Check that equipment ratings and environmental assumptions suit the installation location and system study. |
| AC circuit-breakers | IEC 62271-100 | Requirements and tests for AC circuit-breakers used in high-voltage switchgear and controlgear. | Rated breaking and making capabilities, operating sequence, operating mechanism details, and applicable type-test reports. | Check the breaker’s duties against the system short-circuit study and the specified protection and reclosing requirements. |
| Disconnectors and earthing switches | IEC 62271-102 | Requirements for AC disconnectors and earthing switches, including their applicable switching and withstand duties. | Rated characteristics, interlocking arrangement, operating method, and applicable type-test documentation. | Review the interlocking scheme and confirm that the specified earthing-switch duty matches the installation design. |
| Metal-enclosed switchgear up to and including 52 kV | IEC 62271-200 | AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV; includes classification and design requirements such as internal arc classification where specified. | Switchgear type, rated values, accessibility and internal arc classification (IAC) if required, compartment arrangement, and type-test evidence. | Ensure the offered panel configuration and any IAC classification match the project layout and personnel-access conditions. |
| Gas-insulated switchgear above 52 kV | IEC 62271-203 | Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV. | Rated values, insulation medium and gas-handling information, enclosure details, maintenance requirements, and applicable type-test reports. | Confirm the standard’s voltage scope, project-specific environmental requirements, and applicable gas-management obligations. |
| Cross-equipment quality and delivery records | Applicable IEC product standards and project specification | Document control, manufacturing inspection, testing, identification, and delivery records for the supplied equipment. | Quality plan, inspection and test plan, material records, factory acceptance test procedure, final reports, packing list, and operation and maintenance manuals. | Confirm document completeness, equipment traceability, and agreed witness or hold points before shipment. |